If you are in need of additional power for accessories for your Fire-Lite fire panel then the FCPS24FS6. This is a 6 amp remote power supply with a battery charging circuit that can charge up to an 18 amp battery.
If you have come to the limits of the power outputs on your main panel, then this will give you what you need to use additional bells, sirens, strobes, etc.
This may be used with either a 12 volt or 24 volt system.
Specifications:
Primary (AC) Power
FCPS-24FS6: 120 VAC 60 Hz, 3.2 A maximum
Wire size: minimum 14 AWG (2.0 mm˛) with 600V insulation.
Control Input Circuit
Trigger Input Voltage: 9.0 to 32 VDC.
Trigger Current: 2.0 mA (16 - 32 V).
(per input) 1.0 mA (9 - 16 V).
Trouble Contact Rating
5.0 A at 24 VDC.
Auxiliary Power Output
Specific Application Power - 500 mA maximum.
Output Circuits
+24 VDC filtered, regulated.
3.0 A maximum for any one circuit.
4.0 A maximum total continuous current for all outputs
(Stand-alone mode).
6.0 A maximum total short-term current for all outputs
(NAC Expander mode).
Secondary Power (Battery) Charging Circuit
Supports lead-acid batteries only.
Float Charge Voltage: 27.6VDC.
Maximum Charge Current: 1.5 A.
Maximum Battery Capacity: 18 AH.
Features
- UL Listed NAC Synchronization using System Sensor,
Wheelock or Gentex (Commander Series) appliances.
Cascadable up to 10 power supplies (four with Gentex)
with strobe timing maintained.
Operates as a sync follower or a sync generator (default).
Contains two, fully-isolated input/control circuits (triggered
from FACP Notification Appliance Circuit [NAC
expander mode] or jumpered permanently on [standalone
mode]).
Optional mounting kit, P/N 90286, to internally house
addressable SLC control module (CRF-300 or CMF-
300) for alarm activation.
Four Class B (Style Y) or four Class A (Style Z) (with ZNAC-
4 Module) Notification Appliance Circuits.
6.0 A full load output (3.0 A maximum per circuit) in NAC
expander mode (UL 864).
4.0 A continuous output in stand-alone mode (UL 1481).
In stand-alone mode, output power circuits may be
configured as resettable (reset line from FACP required)
or non-resettable or a mix of two and two.
Fully regulated and filtered power output (optimal for
powering four-wire smoke detectors, annunciators and
other system peripherals requiring regulated/filtered
power).
Power-limiting technology meets UL power-limiting requirements.
Form-C normally-closed trouble relay.
Fully supervised power supply, battery and Notification
Appliance Circuits.
Selectable earth fault detection.
FCPS-24FS6
24 Volt, 6 Amp Remote Power Supply
DF-52301 D-025
Section: Power Supplies/Accessories
July 8, 2004
AC trouble report selectable for immediate or 8 hour
delay.
Works with virtually any UL 864 fire alarm control which
utilizes an industry-standard reverse-polarity notification
circuit (including unfiltered and unregulated bell
power).
Requires input trigger voltage of 9.0 - 32 VDC.
Self-contained in compact, lockable cabinet (15" [38.1
cm] H x 14.5" [36.8 cm] W x 2.75" [7.0 cm] D).
Includes integral battery charger capable of charging up
to 18 AH batteries. Cabinet capable of housing 7.0 AH
batteries.
Battery charger may be disabled via dip switch for applications
requiring larger batteries.
Fixed, clamp-type terminal blocks accommodate up to
12 AWG (3.1 mm˛) wire.