If you have a Silent Knight brand fire panel and you need extra power notification devices such as bells or strobes then the SIL-5495 is a perfect solution for your needs. This 6 amp power supply delivers an extra dose of power for any Silent Knight fire control panel.
It has its own AC power and charging circuits for backup batteries and contains its own backup battery as well. The 5495 can also provide supervision in the following scenarios:
Low AC power Low battery condition Earth ground fault Auxiliary output power limit condition EOL supervision trouble or power limited condition at an output
This power supply will notify the main control of any trouble conditions and create a condition on the main control panel as well. If you would like to add another form of notification then the 5495 also has a Form C relay ouput for trouble conditions.
Specifications:
Electrical Specification AC input: 120 VAC at 2 amps Output: 24 VDC at 6 amps Current: Standby 75 mA Alarm 205 mA Auxiliary power circuit: 1 Notification circuits: 4 Output configuration: 2 Class A (Style Z) 4 Class B (Style Y) (1 Class A & 2 Class B) Amps per output circuit: 3.0 (6.0 amps total) Notification circuit output: 20.4 to 27.3 VDC @ 3.0 amps each, 4.7 kW EOL resistor required on each Class B circuit No. of inputs 2 Input configuration: 2 Class B or 2 Class A Input voltage range: 9 - 32 VDC Battery charging capacity: 35.0 AH Ambient temp.: 32° to 120° F (0° to 49° C)
Mechanical Dimensions: 12.25 W x 16 H x 3 D (30.88 cm W x 40.64 cm H x 7.62 D cm)
Indicator Lights AC power on : Green Battery trouble: Yellow Ground fault: Yellow Aux trouble: Yellow Output troubles (1-4): Yellow
Features UL Listed for 6 amps of notification power Power supply s advanced switch mode design reduces damaging heat and manages power up to 50% more efficiently than other systems Dip switches allow for easy reconfiguration 24 VDC filtered output voltage Four power-limited notification outputs; 2 Class A or 4 Class B, or 1 Class A and 2 Class B Additional continuous auxiliary output 3 amps per output circuit 2 inputs; 2 Class B or 2 Class A Ground fault detector/indicator Independent trouble relay AC loss delay option shuts off power to non-essential high-current accessories like magnetic door holders Built-in synchronization for appliances from System Sensor®,Gentex®, AMSECO®, Wheelock and Faraday Stand alone operation Lightweight design adds to ease of installation and reduces shipping costs Operates with most polarized, UL Listed notification devices ANSI Cadence pattern output capability built-in |